Experts in advanced refrigeration and air-conditioning
Technical information

Data Sheet

Power supply

380/420 V-50 Hz-3 ph (208/230 V-380/575 V-60 Hz-3 ph) Y-Δ PWS DOL

Horsepower

75 hp

Displacement

257 m3

Cooling capacity at ARI conditions, R407C

214,1 kW

Cooling capacity at EN12900 MT conditions, R404A

135,9 kW

Cooling capacity at ARI conditions, R22

220,3 kW

Refrigerant

R22, R404A, R407C

Suction pipe

3 1/8 "

Discharge pipe

2 1/8 "

Weight

560 kg

LRA (PWS)

710 A (50 Hz/380 V)

MCC

171 A

Other remarks

Crankcase heater 300W, Discharge check valve, Includes capacity regulator, Includes oil CPI 170, Oil level switch, Overtemperature Sensor for motor, Suction and discharge temperatures sensors, Suction filter

Sound level

60,4 dB

Accessories

Discharge service valve 2", INT69 Protector, Mounting grommets (4 units), Suction service valve

Application

MHBP

Technology

Fixed speed

Maximum oil temperature

100 °C

Maximum discharge temperature

110 ºC

Maximum winding temperature

110 ºC

Bitzer
CSH7573-90Y
Frascold
C-TSH8 80 240Y
Evolving with you
Enhanced technical support for your projects
Helping you
Reach us via web, phone, mail chat & videoconferencing
International Team
14 nationalities in European Terms
4 wharehouse in Europe
Increased stock availability